Fault CodeAlarm DescriptionSeverityProbable CausesAction
ED Evaporator Water Flow Lost Warning Chilled water pump stopped or failed View Details →
FD Emergency Stop Critical Emergency stop button pressed View Details →
8E Evaporator Entering Water Temperature Sensor Warning Sensor element failure View Details →
AB Evaporator Leaving Water Temperature Sensor Warning Sensor degradation View Details →
A1 Outdoor Air Temperature Sensor Warning Sensor moisture ingress View Details →
D7 Over Voltage Warning Utility voltage surge View Details →
D8 Under Voltage Warning Utility brownout or sag View Details →
F5 High Pressure Cutout - Compressor 1A Critical Condenser coil fouled or airflow blocked View Details →
BA Motor Current Overload - Compressor 1A Warning Compressor motor bearing failure View Details →
C5 Low Chilled Water Temperature: Unit Off Warning Chilled water setpoint too low View Details →
C6 Low Chilled Water Temperature: Unit On Warning Evaporator flow too low while running View Details →
B5 Low Suction Refrigerant Pressure - Circuit 1 Warning Low refrigerant charge View Details →
198 Low Oil Flow - Compressor 1A Critical Oil filter clogged View Details →
1C6 High Differential Refrigerant Pressure - Circuit 1 Critical Condenser water temperature too high View Details →
1DE High Oil Temperature - Compressor 1A Warning Oil cooler fouled or bypassed View Details →
398 BAS Communication Lost Warning BAS network cable disconnected View Details →
A2 Condenser Air Temperature Sensor Warning Sensor element failure View Details →
A3 Economizer Leaving Water Temperature Sensor Warning Economizer sensor failure View Details →
A4 Chilled Water Entering Temperature Sensor Warning Sensor drift or failure View Details →
AC Chilled Water Leaving Temperature Sensor Warning Sensor element failure View Details →
D1 Suction Pressure Sensor - Circuit 1 Warning Pressure sensor element failure View Details →
D2 Discharge Pressure Sensor - Circuit 1 Warning Discharge pressure sensor failure View Details →
D3 Suction Pressure Sensor - Circuit 2 Warning Circuit 2 suction sensor failure View Details →
D4 Discharge Pressure Sensor - Circuit 2 Warning Circuit 2 discharge sensor failure View Details →
D5 Oil Pressure Sensor Warning Oil pressure sensor element failure View Details →
D6 Oil Temperature Sensor Warning Oil temperature sensor failure View Details →
D9 Compressor Motor Temperature Sensor Warning Motor winding temperature sensor failure View Details →
B6 Low Suction Refrigerant Pressure - Circuit 2 Warning Low refrigerant charge on circuit 2 View Details →
F6 High Pressure Cutout - Compressor 2A Critical Condenser coil fouled View Details →
BB Motor Current Overload - Compressor 2A Warning Compressor 2A motor bearing failure View Details →
199 Low Oil Flow - Compressor 2A Critical Oil filter clogged on circuit 2 View Details →
1C7 High Differential Refrigerant Pressure - Circuit 2 Critical Condenser water temp too high on circuit 2 View Details →
1DF High Oil Temperature - Compressor 2A Warning Oil cooler on circuit 2 fouled View Details →
2E7 High Condenser Refrigerant Temperature - Circuit 2 Warning Condenser water flow too low on circuit 2 View Details →