Trane RTAC Fault Code B6
Trane RTAC Fault Code B6 is a warning alarm indicating: Low Suction Refrigerant Pressure - Circuit 2. The most common causes include Low refrigerant charge on circuit 2. Estimated repair time: 2-4 hours (requires leak repair, evacuation, and refrigerant recharge). This alarm requires immediate attention by a certified HVAC technician.
Alarm Description
Low Suction Refrigerant Pressure - Circuit 2
Brand: Trane | Model: RTAC (Screw Compressor Chiller) | Code: B6 | Severity: Warning
Observable Symptoms
- Suction pressure gauge reads below normal operating range
- Compressor may short cycle or run continuously without cooling
- Frost may appear on suction line or evaporator
What to Check First
Before diving into detailed diagnostics, start with this quick first check:
Probable Causes
- Low refrigerant charge on circuit 2
- Expansion valve 2 starving
- Evaporator flow low on circuit 2
- Fouled evaporator
Recommended Inspection Steps
- Check superheat on circuit 2
- Inspect expansion valve 2
- Measure water flow
- Add refrigerant if low
Required Tools & Equipment
- Coil cleaning brush and coil cleaner
- PT chart for refrigerant type
- Safety PPE (gloves, safety glasses, face shield)
Estimated Repair Time
2-4 hours (requires leak repair, evacuation, and refrigerant recharge)
When to Call a Professional
- If the fault persists after completing all recommended inspection steps
- If you observe unusual noises, vibrations, or oil leaks from the compressor
- If refrigerant charge levels are outside OEM specifications and EPA-certified recovery is needed
- If electrical measurements show voltage imbalance greater than 2% between phases
- If the fault recurs immediately after reset, indicating an unresolved safety condition
- Contact an authorized Trane service representative for warranty-covered repairs
Related Fault Codes
Other Trane RTAC codes that may be related:
OEM Service Manual Reference
OEM Reference: Trane RTAC Air-Cooled Rotary Screw Chiller Service Manual (SVR-SVN001-EN). Available through Trane Commercial support.
Frequently Asked Questions
What does Trane RTAC fault code B6 mean?
Fault code B6 on a Trane RTAC chiller indicates: Low Suction Refrigerant Pressure - Circuit 2. This is a warning alarm that requires diagnostic attention.
What causes Trane RTAC alarm code B6?
Common causes include: Low refrigerant charge on circuit 2; Expansion valve 2 starving; Evaporator flow low on circuit 2
How do I fix Trane RTAC error code B6?
Follow the recommended inspection steps below. Start with the quick check, then proceed through each step. If the fault persists after all steps, contact an authorized Trane service representative.