OEM Service Manual: Carrier 30XW (AquaForce) Installation, Operation and Maintenance Manual. Available through Carrier Commercial Systems.
30 codes
Fault CodeAlarm DescriptionSeverityProbable CausesAction
1 Evaporator entering water temperature sensor fault Warning Sensor element failure View Details →
2 Evaporator leaving water temperature sensor fault Warning Sensor element degradation View Details →
3 Condenser entering water temperature sensor fault Warning Sensor failure View Details →
7 Outdoor air temperature sensor fault Warning Sensor moisture ingress View Details →
14 Discharge pressure transducer fault Warning Transducer element failure View Details →
16 Suction pressure transducer fault Warning Transducer port blocked View Details →
30 CCN communication fault Warning CCN cable damaged View Details →
41 Emergency stop Critical E-stop button activated View Details →
44 Discharge pressure too high Critical Condenser water flow low View Details →
54 Oil level low Critical Oil leak through system View Details →
56 Low saturated suction temperature Warning Low refrigerant charge View Details →
68 Low oil pressure Critical Oil pump wear View Details →
72 Evaporator frost protection Critical Low water flow View Details →
77 High compressor motor current Warning Motor bearing failure View Details →
85 High motor winding temperature Warning Motor cooling insufficient View Details →
4 Condenser leaving water temperature sensor fault Warning Sensor element failure View Details →
5 Defrost thermistor failure Warning Sensor element degraded View Details →
6 Remote temperature sensor failure Warning Remote sensor failure View Details →
8 Compressor A2 discharge temperature sensor fault Warning Sensor element failure View Details →
10 Compressor B1 discharge temperature sensor fault Warning Sensor failure on circuit B View Details →
15 Discharge pressure transducer failure circuit B Warning Transducer diaphragm damaged View Details →
17 Suction pressure transducer failure circuit B Warning Sensing port blocked View Details →
20 Compressor motor overload circuit A Critical Motor drawing excessive current View Details →
21 Compressor motor overload circuit B Critical Motor overload on circuit B View Details →
31 Loss of communication with SCPM B1 Warning CCN cable to circuit B damaged View Details →
38 Power supply error Warning Phase voltage imbalance View Details →
45 Discharge pressure circuit B too high Warning Condenser B fouling View Details →
46 Suction pressure circuit A too low Warning Low refrigerant on circuit A View Details →
47 Suction pressure circuit B too low Warning Low refrigerant on circuit B View Details →
55 Oil level circuit B low Warning Refrigerant leak on B carrying oil View Details →
[PDF] Quick Reference Card Download printable PDF for 30XW fault codes Download PDF
Disclaimer: All Carrier 30XW fault code data is for reference only. Do not use this information to replace certified professional HVAC technician judgment. Always refer to original OEM official service manual.